UNIT SHUTDOWN DUE TO FIRE IN THE TURBINE BUILDING CAUSED BY ELECTRICAL EQUIPMENT FAILURE

At 19:46 TG-4 was being taken out of service for maintenance. When it was almost completely stopped at 20:09 spontaneous breaker closure occurred and the TG was connected to the grid. Due to this the generator was transferred to the motor regime of operation, which resulted in the loss of tightness in the generator cooling system, discharge and ignition of hydrogen and oil in the location of generator bearings. At 20:10 personnel scrammed the reactor by pressing emergency protection button and called the fire brigade. TG-3 was stopped, the oil from the TGs was drained and hydrogen in the generators was replaced by nitrogen. On the signal of reactor emergency protection deenergization the DGs started as designed. Due to hydrogen release to the turbine building and its reburn under the roof, part of the roof above TG-4 collapsed. The automatic fire-fighting systems actuated as designed. The firemen that arrived fulfilled their job successfully. By 23:30 the fire was completely extinguished. The reactor was cooled down according to Technical Specification. Nobody was injured. Radioactivity releases to environment did not occur.

Location: CHERNOBYL-2
Event date: Fri, 11-10-1991